The ioLogik E1200 Series supports the most often-used protocols for retrieving I/O data, making it capable of handling a wide variety of applications. Most IT engineers use SNMP or RESTful API protocols, but OT engineers are more familiar with OT-based protocols, such as Modbus and EtherNet/IP. Moxa’s Smart I/O makes it possible for both IT and OT engineers to conveniently retrieve data from the same I/O device. The ioLogik E1200 Series speaks six different protocols, including Modbus TCP, EtherNet/IP, and Moxa AOPC for OT engineers, as well as SNMP, RESTful API, and Moxa MXIO library for IT engineers. The ioLogik E1200 retrieves I/O data and converts the data to any of these protocols at the same time, allowing you to get your applications connected easily and effortlessly.

Specifications

Input/Output Interface

Digital Input Channels

  • ioLogik E1210 models: 16
  • ioLogik E1212/E1213 models: 8
  • ioLogik E1214 models: 6
  • ioLogik E1242 models: 4

Digital Output Channels

  • ioLogik E1211 models: 16
  • ioLogik E1213 models: 4

Configurable DIO Channels (by jumper)

  • ioLogik E1212 models: 8
  • ioLogik E1213/E1242 models: 4

Relay Channels

  • ioLogik E1214 models: 6

Analog Input Channels

  • ioLogik E1240 models: 8
  • ioLogik E1242 models: 4

Analog Output Channels

  • ioLogik E1241 models: 4

RTD Channels

  • ioLogik E1260 models: 6

Thermocouple Channels

  • ioLogik E1262 models: 8

Isolation

  • 3k VDC or 2k Vrms

Buttons

  • Reset button

Connector:

  • Screw-fastened Euroblock terminal

Sensor Type:

  • Dry contact
  • Wet contact (NPN or PNP)

I/O Mode:

  • DI or event counter

Dry Contact:

  • On: short to GND
  • Off: open

Wet Contact (DI to COM):

  • On: 10 to 30 VDC
  • Off: 0 to 3 VDC

Counter Frequency:

  • 250 Hz

Digital Filtering Time Interval:

  • Software configurable

Points per COM:

  • ioLogik E1210/E1212 Series: 8 channels
  • ioLogik E1213 Series: 12 channels
  • ioLogik E1214 Series: 6 channels
  • ioLogik E1242 Series: 4 channels

Connector

  • Screw-fastened Euroblock terminal

I/O Type

  • ioLogik E1211/E1212/E1242 models: Sink
  • ioLogik E1213 models: Source

I/O Mode

  • DO or pulse output

Current Rating

  • ioLogik E1211/E1212/E1242 models: 200 mA per channel
  • ioLogik E1213 models: 500 mA per channel

Pulse Output Frequency

  • 500 Hz (max.)

Over-Current Protection

  • ioLogik E1211/E1212/E1242 models: 2.6 A per channel @ 25°C
  • ioLogik E1213 models: 1.5 A per channel @ 25°C

Over-Temperature Shutdown

  • 175°C (typical), 150°C (min.)

Over-Voltage Protection

  • 35 VDC

Connector

  • Screw-fastened Euroblock terminal

Type

  • Form A (N.O.) power relay

I/O Mode

  • Relay or pulse output

Pulse Output Frequency

  • 0.3 Hz at rated load (max.)

Contact Current Rating

  • ioLogik E1214/E1214-T models:
    • Resistive load:
      • 5A @ 30 VDC, 250 VAC, 110 VAC

Contact Resistance

  • 100 milli-ohms (max.)

Mechanical Endurance

  • 5,000,000 operations

Electrical Endurance

  • 100,000 operations @ 5 A resistive load

Breakdown Voltage

  • 500 VAC

Initial Insulation Resistance

  • 1,000 mega-ohms (min.) @ 500 VDC

Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.

Connector

  • Screw-fastened Euroblock terminal

I/O Mode

  • Voltage/Current

I/O Type

  • Differential

Resolution

  • 16 bits

Input Range

  • 0 to 10 VDC
  • 0 to 20 mA
  • 4 to 20 mA
  • 4 to 20 mA (with burn-out detection)

Accuracy

  • ioLogik E1240/E1242:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -10 to 60°C
  • ioLogik E1240-T/E1242-T:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -10 to 60°C
    • ±0.5% FSR @ -40 to 75°C

Sampling Rate

  • ioLogik E1240: 12 samples/sec per module (shared between up to 8 channels)
  • ioLogik E1242: 12 samples/sec per module (shared between up to 4 channels)

Built-in Resistor for Current Input

  • 120 ohms

Input Impedance

  • 10 mega-ohms (min.)

Connector:

  • Screw-fastened Euroblock terminal

I/O Mode:

  • Voltage/Current

Output Range:

  • 0 to 10 VDC
  • 0 to 20 mA
  • 4 to 20 mA

Resolution:

  • 12-bit

Accuracy:

  • ioLogik E1241:
    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -10 to 60°C
  • ioLogik E1241-T:
    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -40 to 75°C

Load (Current Mode):

  • Internal power: 400 ohms (max.)
  • 24 V external power: 1000 ohms (max.)

Voltage Output Short-Circuit Protection:

  • 10 mA

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • PT1000 (-200 to 350°C)
  • PT50, PT100, PT200, PT500 (-200 to 850°C)

Resistance Type

  • 310, 620, 1250, and 2200 ohms

Input Connection

  • 2- or 3-wire

Sampling Rate

  • ioLogik E1260: 12 samples/sec per module (shared between up to 6 channels)

Resolution

  • 0.1°C or 0.1 ohms

Accuracy

  • ioLogik E1260:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -10 to 60°C
  • ioLogik E1260-T:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -40 to 75°C

Input Impedance

  • 625 kilo-ohms (min.)

Connector

  • Screw-fastened Euroblock terminal

Sensor Type

  • J, K, T, E, R, S, B, N

Millivolt Type

  • ±19.532 mV
  • ±39.062 mV
  • ±78.126 mV
  • Fault and over-voltage protection:
    • -35 to +35 VDC (power off)
    • -25 to +30 VDC (power on)

Resolution

  • 16 bits

Millivolt Accuracy

  • ioLogik E1262:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -10 to 60°C
  • ioLogik E1262-T:

    • ±0.1% FSR @ 25°C
    • ±0.3% FSR @ -40 to 75°C

TC Accuracy

  • Types J, T, E, S, B: ±5°C
  • Types K, R, N: ±8°C

CJC Accuracy

  • ±0.5°C @ 25°C
  • ±1.5°C @ -40 to 75°C

Sampling Rate

  • ioLogik E1262: 12 samples/sec per module (shared between up to 8 channels)

Input Impedance

  • 10 mega-ohms (min.)

10/100BaseT(X) Ports (RJ45 connector):

  • 2, 1 MAC address (Ethernet bypass)

Magnetic Isolation Protection:

  • 1.5 kV (built-in)

Configuration Options:

  • Web Console (HTTP)
  • Windows Utility (ioSearch)
  • MCC Tool

Industrial Protocols:

  • Modbus TCP Server (Slave)
  • Moxa AOPC (Active Tag)
  • MXIO Library
  • EtherNet/IP Adapter

Management:

  • RESTful API
  • SNMPv1/v2c
  • SNMPv1 Trap
  • HTTP
  • DHCP Client
  • BOOTP
  • IPv4
  • TCP/IP
  • UDP

MIB:

  • Device Settings MIB

Security:

  • Access control list

Authentication:

  • Local database

LED Indicators:

  • Power, Ready, Port 1, Port 2

Functions Supported

  • 1, 2, 3, 4, 5, 6, 15, 16, 23

Mode

  • Server (Slave)

Max. No. of Client Connections

  • 10

Mode: 

  • Adapter

Max. No. of Scanner Connections:

  • 9 (for read-only), 1 (for read/write)

Power Connector:

  • Screw-fastened Euroblock terminal

No. of Power Inputs:

  • 1

Input Voltage:

  • 12 to 36 VDC

Power Consumption:

  • ioLogik E1210 Series: 110 mA @ 24 VDC
  • ioLogik E1211 Series: 200 mA @ 24 VDC
  • ioLogik E1212 Series: 155 mA @ 24 VDC
  • ioLogik E1213 Series: 130 mA @ 24 VDC
  • ioLogik E1214 Series: 188 mA @ 24 VDC
  • ioLogik E1240 Series: 121 mA @ 24 VDC
  • ioLogik E1241 Series: 194 mA @ 24 VDC
  • ioLogik E1242 Series: 139 mA @ 24 VDC
  • ioLogik E1260 Series: 110 mA @ 24 VDC
  • ioLogik E1262 Series: 118 mA @ 24 VDC

Housing

  • Plastic

Dimensions

  • 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)

Weight

  • 200 g (0.44 lb)

Installation

  • DIN-rail mounting
  • Wall mounting

Wiring

  • I/O cable, 16 to 26 AWG
  • Power cable, 12 to 24 AWG

Operating Temperature

  • Standard models: -10 to 60°C (14 to 140°F)
  • Wide temp. models: -40 to 75°C (-40 to 167°F)

Storage Temperature (package included)

  • -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

  • 5 to 95% (non-condensing)

Altitude

  • 4000 m

EMC

  • EN 55032/24
  • EN 61000-6-2/-6-4

EMI

  • CISPR 32, FCC Part 15B Class A

EMS

  • IEC 61000-4-2 ESD:
    • Contact: 4 kV
    • Air: 8 kV
  • IEC 61000-4-3 RS: 80 MHz to 1 GHz:
    • 10 V/m
  • IEC 61000-4-4 EFT:
    • Power: 2 kV
    • Signal: 1 kV
  • IEC 61000-4-5 Surge:
    • Power: 2 kV
    • Signal: 1 kV
  • IEC 61000-4-6 CS:
    • 10 V
  • IEC 61000-4-8 PFMF

Hazardous Locations

  • ATEX, Class I Division 2

Safety

  • UL 508

Shock

  • IEC 60068-2-27

Freefall

  • IEC 60068-2-32

Vibration

  • IEC 60068-2-6

Green Product:

  • RoHS, CRoHS, WEEE

Time

  • ioLogik E1210 models: 671,345 hrs
  • ioLogik E1211 models: 923,027 hrs
  • ioLogik E1212 models: 561,930 hrs
  • ioLogik E1213 models: 715,256 hrs
  • ioLogik E1214 models: 808,744 hrs
  • ioLogik E1240 models: 474,053 hrs
  • ioLogik E1241 models: 888,656 hrs
  • ioLogik E1242 models: 502,210 hrs
  • ioLogik E1260 models: 660,260 hrs
  • ioLogik E1262 models: 631,418 hrs

Standards

  • Telcordia Standard SR-332

Warranty Period:

  • ioLogik E1214: 2 years
  • ioLogik E1210/E1211/E1212/E1213/E1240/E1241/E1242/E1260/E1262: 5 years